Regulatory Notice

Due to recent EPA regulations under the AIM Act, R-134a refrigerant is now restricted in new equipment manufacturing. Aspen Systems can continue to supply R-134a-based LCM modules for qualifying EPA-exempt and military programs.

For new commercial designs, Aspen offers fully compliant next-generation G-Series liquid chiller modules using approved low-GWP refrigerants.

Upgrade to our AIM Act Compliant 600 G-Series Liquid Chiller Module

Liquid Chiller Module, LCM-600

Cooling Capacity Graph, Compact, 600w Fluid Chiller, LCM600
LCM-600
Cooling Capacity See graph
Maximum Current 15 Amps
*Maximum Power Draw 360 Watts (at 24 V)
Voltage 22-30 VDC
Operating Ambient Temperature 0 to 50°C (32 to 122°F)
Coolant Temperature 0 to 50°C (32 to 122°F)
Storage Temperature -20 to 50°C (-4 to 122°F)
Compatible Fluids Water, Glycol/Water Mixtures
Refrigerant R134a
Orientation Must operate within 30° of vertical
Weight 2.7 kg (6.0 lbs)
Dimensions 134H x 199W x 161D mm (5.3H x 7.8W x 6.3D in)

Get a Quote | Application Questions

Please send us your requests; our team is happy to help.
You can also reach us by email at:  info@aspensystems.com
or by phone number at (508) 281-5322